Series 630

When your project requires a listed rolling service fire door, the 630 Series provides a better all-around solution. The 630 Series is designed to meet the most stringent fire safety standards in a range of labels, sizes, and mounting options. These NFPA-80-compliant doors are also available in a variety of slat profiles, material finishes and colors — so you won’t have to sacrifice style in favor of functionality.


Standard Features

  • Available with UL and FM 3-Hour Labels for Doors Up to 12' (3658 mm) Wide or High

  • Available with UL Oversize Label for Doors Up to 14' (4267 mm) Wide or High

  • NFPA-80 Compliant

  • Labeled to Meet New York City and California State Fire Marshall Fire Safety Standards

  • Fusible Link Separates at 165-Degrees F (74-Degrees C) to Automatically Close the Door

  • Governor Controls Rate of Door Descent During a Fire

  • UL-Listed Welded Wall Angle for Face-to-Wall Applications in Masonry Fire Walls Eliminates Drill and Tap Processes

  • 1 1/2-Hour UL Label for Non-Masonry Applications
  • Guide Assemble Rest on Sill for Flush Guide Installation

  • Locking Standards

  • Slide Bolt on Push-Up and Crank

  • Drive Train on Motor


Options

  • Fire Sentinel Time-Delay Release Device
  • Fire Minuteman Reset Hoist
  • FireLite Vision Lites in 4-, 3-, and 1 1/2-Hour Labels
  • UL-Listed Brush-Type Smoke Gaskets
  • Photoelectric or Ionization-Type Smoke Detectors
  • Chain Hoist (Below 80 sq. ft. or 7432 sq. mm), Crank or Electric Operation
  • Powder-Coat Paint Finish in 21 Standard Colors, Custom Colors, or Color-Matched to Architect's Specification Available



Part 1 General

1.01 Work Included
The doors will be 630 Series as manufactured by Overhead Door Corporation.

1.02 Related Work
Opening preparation, miscellaneous or structural metal work, access panels, finish or field painting, field electrical wiring, wire, conduit, fuses and disconnect switches are in the Scope of Work of other divisions or trades.

1.03 Quality Assurance
In accordance with accepted quality assurance guidelines for motor-operated doors, both the door and electric operator (optional) shall be manufactured by a single-source producer of door systems; as by Overhead Door Corporation.

Part 2 Product

2.01 Curtain
Curtain will be interlocking roll-formed slats as specified following. Endlocks will be attached to each end of alternate slats to prevent lateral movement.

    Curved profile type C-187 for doors thru 14'0" (4267 mm) wide by 12'0" (3658 mm) high, fabricated of 22 gauge galvanized steel. (Optional 20 ga. galvanized or 22 ga. stainless steel).

    Curved profile type C-187 for doors over 14'0" (4267 mm) thru 20'0" (6096 mm) wide, fabricated of 20 gauge galvanized steel. (Optional 18 ga. galvanized or 20 ga. stainless steel).

    Curved profile type C-275 for doors thru 14'0" (4267 mm) wide by 12'0" (3658 mm) high, fabricated of 22 gauge galvanized steel. (Optional 20 ga. galvanized or 22 ga. stainless steel).

    Curved profile type C-275 for doors over 14'0" (4267 mm) thru 20'0" (3658 mm) wide, fabricated of 20 gauge galvanized steel. (Optional 18 ga. galvanized or 20 ga. stainless steel).

    Curved profile type C-275 for doors over 20'0" (6096 mm) thru 41'2" (12548 mm) wide, fabricated of 18 gauge galvanized steel. (Optional 16 ga. galvanized steel).

    Flat profile type F-265 for doors thru 14'0" (4267 mm) wide by 12'0" (3658 mm) high, fabricated of 22 gauge galvanized steel. (Optional 20 ga. galvanized or 22 ga. stainless steel).

    Flat profile type F-265 for doors over 14'0" (4267 mm) thru 20'0" (6096 mm) wide, fabricated of 20 gauge galvanized steel. (Optional 18 ga. galvanized or 20 ga. stainless steel).

    Flat profile type F-265 for doors over 20'0" (6096 mm) thru 41'2" (12548 mm) wide, fabricated of 18 gauge galvanized steel.

2.02 Bottom Bar
Bottom bar will be two back to back structural steel angles 1 1/2" (38 mm) by 1 1/2" (38 mm) by 1/8" (3 mm) minimum. (Optional single angle for conveyor applications.) (Optional galvanized or stainless steel.) (Optional sloping bottom bar within UL limits)

2.03 Guides
Guides will be roll-formed steel shapes attached to continuous steel wall angle for doors thru 12' (3658 mm) wide. Three structural steel angles with minimum thickness of 3/16" (5 mm) for doors over 12' (3658 mm) wide. Guides for between jamb doors will be structural angles.

2.04 Brackets
Brackets will be steel plate to support counterbalance, curtain and hood.

2.05 Counterbalance
Counterbalance will be helical torsion spring type housed in a steel tube or pipe barrel, supporting the curtain with deflection limited to 0.03" (0.75 mm) per foot of span. Counterbalance will be adjustable.

2.06 Hood
Hood will be 24 gauge galvanized primed steel minimum for wall openings thru 19' (5791 mm) wide. 22 gauge galvanized primed steel for wall openings over 19' (5791 mm) wide. Hood will be equipped with thermally controlled, internal, galvanized steel flame baffle. Provide one intermediate support bracket for wall openings over 13'6" (4115 mm) wide and two support brackets for wall openings over 19'0" (5791 mm) wide.

2.07 Finish
Steel slats and hood will be galvanized in accordance with ASTM A 653 and receive rust-inhibitive, roll coating process, including 0.2 mils thick baked-on prime paint, and 0.6 mils thick baked-on polyester gray (optional tan) (optional powder coated) top coat. Non-galvanized exposed ferrous surfaces shall receive one coat of rust-inhibitive primer. (Optional stainless steel slats will be 2B mill finish or No. 4 satin finish).

2.08 Color
Polyester top coat shall be grey or tan. (Powder coating finish in color is optional.)

2.09 Glazing
(Optional fire-rated vision panels, up to four glazing panels 3" (76 mm) by 5/8" (16 mm); FireLite glazing as manufactured by Nippon Electric Glass Co.) Available on 4 hour, 3 hour, and 90 minute label doors.

2.10 Operation
Standard operation will be manual push up to approximately 80 sq. ft. (7432 sq. mm), standard chain operation over approximately 80 sq. ft. (7432 sq. mm) (Optional chain hoist, crank). Optional electric motor operation will be UL listed electric operator, size as recommended by manufacturer to move door in either direction at not less than 2/3 foot (203 mm) nor more than 1 foot (305 mm) per second. (Optional sensing edge protection will be Pneumatic or Electric. Electric sensing edge available as a 2 wire or 4 wire "Fail-Safe" version).
Operator controls will be Push-button (Optional Key or Keyed push-button) operated control stations with open, close and stop buttons for surface (flush) mounting, for interior (exterior) (both interior and exterior) location.

2.11 Automatic Closure
Automatic closure, thermally controlled by means of 165 degree or 212 degree fusible links. Operating mechanism will be disengaged during automatic closing. Automatic closing rate will be controlled by a governor.
(Optional "Fail-Safe" Time Delay Release Device, UL and UL 864 rated; Fire Sentinel Model A, Model B, Model B 2, B2 master/slave and Model C.
(Automatic Closure on alarm available by 3 modes initiated by central fire alarm system)
*Fire sentinel releases to close door on alarm
*Fire sentinel closes electrically operated fire door electrically on alarm** when
power is on
*Fire sentinel closes electrically operator fire doors electrically on alarm** when
power is off and uninterrupted power supply (UPS) is provided with electrical
operator.

2.12 Locking
(Optional locking mechanisms include interior bottom bar slide bolt, interior slide lock for electric operation with interlock switch or cylinder locking bottom bar with mortise cylinders.)

2.13 Wall Mounting Condition
Standard mounting wall be face-of-wall mounting (Optional between jambs mounting.)

2.14 Label

    Rolling fire doors up to 144 sq. ft. (13378 sq. mm) and 12' (3658 mm) in width or height shall bear the (UL and FM 3-Hour Label). (UL 3-Hour label.) (UL and FM 1 1/2-Hour Label for non-masonry fire walls.)

    Rolling fire doors over 144 sq. ft. (13378 sq. mm) will receive the UL Oversize Fire Door Label.

    Rolling fire doors over 144 sq. ft. (13378 sq. mm) and not exceeding 18' (5486 mm) in height or width will receive the Factory Mutual Label for Oversize Fire Doors. Doors over 18' must be reviewed by FM.

Part 3 Execution

3.01 Installation
Install the door in accordance with Overhead Door Corporation instructions and standards using an authorized Overhead Door Corporation Distributor or representative. Install Rolling Fire Doors in compliance with the requirements of NFPA 80.

3.02 Testing
Test fire-release system and reset components after testing. Instruct owner's personnel in proper operating procedures and maintenance schedules.

* Note to specifiers: Words in parentheses indicate frequently specified and highly recommended options.
** Safety sensing edge required.