The 631 Series rolling steel, fire-rated service doors offer superior protection wherever a listed fire door is required. Common applications include factories, warehouses, mills, distribution centers and parking garages. Customized fire doors are available for conveyor openings. These doors feature fusible links mounted on both sides of the wall that separate to automatically close the door. UL recommends a 165°F (74°C) fuse link for ambient conditions for 100°F (38°C) or less, or a 212°F (100°C) fuse link for ambient conditions over 100°F (38°C). Added protection features, such as Fire Sentinel and FireLite vision lites are optional.
Standard Features
-
Available with UL 3-Hour Labels for Doors up to 12' (3658 mm) Wide or High
-
NFPA-80 Compliant
-
Labeled to Meet New York City and California State Fire Marshall Fire Safety Standards
-
Fusible Link Separates at 165-Degrees F (74-Degrees C) to Automatically Close the Door
-
Governor Controls Rate of Door Descent During a Fire
-
UL-Listed Face-to-Wall Applications in Masonry Fire Walls Eliminates Drill and Tap Processes
- 1 1/2-Hour UL Label for Non-Masonry Applications
-
Guide Assemble Rest on Sill for Flush Guide Installation
-
Locking Standards
-
Slide Bolt on Push-Up and Crank
-
Drive Train on Motor
Options
- Fire Sentinel Time-Delay Release Device
- Fire Minuteman Reset Hoist
- FireLite Vision Lites in 4-, 3-, and 1 1/2-Hour Labels
- UL-Listed Brush-Type Smoke Gaskets
- Photoelectric or Ionization-Type Smoke Detectors
- Chain Hoist (Below 80 sq. ft. or 7432 sq. mm), Crank or Electric Operation
- Powder-Coat Paint Finish in 21 Standard Colors, Custom Colors, or Color-Matched to Architect's Specification Available
Part 1 General
1.01 Work Included
The doors will be 631 Series as manufactured by Overhead Door Corporation.
1.02 Related Work
Opening preparation, miscellaneous or structural metal work, access panels, finish or field painting, field electrical wiring, wire, conduit, fuses and disconnect switches are in the Scope of Work of other divisions or trades.
1.03 Quality Assurance
In accordance with accepted quality assurance guidelines for motor-operated doors, both the door and electric operator (optional) shall be manufactured by a single-source producer of door systems; as by Overhead Door Corporation.
Part 2 Product
2.01 Curtain
Curtain will be interlocking roll-formed slats as specified following. Endlocks will be attached to each end of alternate slats to prevent lateral movement.
-
Curved profile type C-187 for doors thru 14'0" (4267 mm) wide, fabricated of 24 gauge galvanized steel.
Flat profile type F-265 for doors thru 14'0" (4267 mm) wide, fabricated of 24 gauge galvanized steel.
2.02 Bottom Bar
Bottom bar will be two back to back structural steel angles 1 1/2" (38 mm) by 1 1/2" (38 mm) by 1/8" (3 mm) minimum. (Optional single angle for conveyor applications.) (Optional galvanized or stainless steel.) (Optional sloping bottom bar within UL limits)
2.03 Guides
Guides will be roll-formed steel shapes attached to continuous steel wall angle for doors thru 12' (3658 mm) wide. Three structural steel angles with minimum thickness of 3/16" (5 mm) for doors over 12' (3658 mm) wide. Guides for between jamb doors will be structural angles.
2.04 Brackets
Brackets will be steel plate to support counterbalance, curtain and hood.
2.05 Counterbalance
Counterbalance will be helical torsion spring type housed in a steel tube or pipe barrel, supporting the curtain with deflection limited to 0.03" (0.75 mm) per foot of span. Counterbalance will be adjustable.
2.06 Hood
Hood will be 24 gauge galvanized primed steel. Hood will include one intermediate support bracket for openings over 13'6" (4115 mm) wide.
2.07 Finish
Steel slats and hood will be galvanized in accordance with ASTM A 653 and receive rust-inhibitive, roll coating process, including 0.2 mils thick baked-on prime paint, and 0.6 mils thick baked-on polyester gray (optional tan) (optional powder coated) top coat. Non-galvanized exposed ferrous surfaces shall receive one coat of rust-inhibitive primer. (Optional stainless steel slats will be 2B mill finish or No. 4 satin finish).
2.08 Color
Polyester top coat shall be grey or tan. (Powder coating finish in color is optional.)
2.09 Glazing
(Optional fire-rated vision panels, up to four glazing panels 3" (76 mm) by 5/8" (16 mm); FireLite glazing as manufactured by Nippon Electric Glass Co.) Available on 4 hour, 3 hour, and 90 minute label doors.
2.10 Operation
Standard operation will be manual push up to approximately 80 sq. ft. (7432 sq. mm), standard chain operation over approximately 80 sq. ft. (7432 sq. mm) (Optional chain hoist, crank). Optional electric motor operation will be UL listed electric operator, size as recommended by manufacturer to move door in either direction at not less than 2/3 foot (203 mm) nor more than 1 foot (305 mm) per second. (Optional sensing edge protection will be Pneumatic or Electric. Electric sensing edge available as a 2 wire or 4 wire "Fail-Safe" version).
Operator controls will be Push-button (Optional Key or Keyed push-button) operated control stations with open, close and stop buttons for surface (flush) mounting, for interior (exterior) (both interior and exterior) location.
2.11 Automatic Closure
Automatic closure, thermally controlled by means of 165 degree or 212 degree fusible links. Operating mechanism will be disengaged during automatic closing. Automatic closing rate will be controlled by a governor.
(Optional "Fail-Safe" Time Delay Release Device, UL and UL 864 rated; Fire Sentinel Model A, Model B, Model B 2, B2 master/slave and Model C.
(Automatic Closure on alarm available by 3 modes initiated by central fire alarm system)
*Fire sentinel releases to close door on alarm
*Fire sentinel closes electrically operated fire door electrically on alarm** when
power is on
*Fire sentinel closes electrically operator fire doors electrically on alarm** when
power is off and uninterrupted power supply (UPS) is provided with electrical
operator.
2.12 Locking
(Optional locking mechanisms include interior bottom bar slide bolt, interior slide lock for electric operation with interlock switch or cylinder locking bottom bar with mortise cylinders.)
2.13 Wall Mounting Condition
Standard mounting wall be face-of-wall mounting (Optional between jambs mounting.)
2.14 Label
- Rolling fire doors up to 144 sq. ft. (13378 sq. mm) and 12' (3658 mm) in width or height shall bear the UL 3-Hour Label and the UL 1 1/2-Hour Label for non-masonry fire walls.
Oversized Fire Door Label. Maximum authorized wall opening is 14'0" (4267 mm) wide x 12'0" (3658 mm) high.
Rolling fire doors up to 144 sq. ft. (13378 sq. mm) and 12' (3658 mm) in width and height will bear the UL 4-Hour Label.
Rolling fire doors over 144 sq. ft. (13378 sq. mm) or over 12' (3658 mm) in width or height will receive the UL Oversize Fire Door Label.
Part 3 Execution
3.01 Installation
Install the door in accordance with Overhead Door Corporation instructions and standards using an authorized Overhead Door Corporation Distributor or representative. Install Rolling Fire Doors in compliance with the requirements of NFPA 80.
3.02 Testing
Test fire-release system and reset components after testing. Instruct owner's personnel in proper operating procedures and maintenance schedules.
* Note to specifiers: Words in parentheses indicate frequently specified and highly recommended options.